True dual-turn, high-performance online UPS
The DS Power 300T Series uses the latest DSP technology that can be programmed to suit a wide range of electrical environments without compromising UPS performance. With the DS Power series, efficiency, reliability and functionality have been increased to levels unattainable with legacy analog technology. This technology only creates significant increases in MTBF. Not only that, but also the DSP's ability to process signals accurately at a very high speed, it allows all UPS subsystems to be controlled with greatly increased accuracy.
Genel Özellikler
• Output isolation transformer
• Optional SNMP and MODBUS adapters
• High input power factor
• High efficiency up to 93.5%
• Cold start feature
• Static and maintenance bypass switch
• Short-circuit and overload protection at output
• External REPO input
• 512 event recording (512 events, 45000 alarms)
• Clock and calendar
• Automatic battery test, remaining battery time display
• Heat compensated charging system
• 2 RS232 serial ports and 12 dry contact outputs
• Modular structure controlled by 3 DSPs
• Low current harmonic distortion at input
• Optional graphic panel
• Optional usb memory
• Manufactured according to EC EN62040 directive
• Fully digital structure
• Small footprint
• Eco mode operation (optional)
• Fewer electronic components
• Enhanced control of input
• Selectable input / output voltage / frequency range
• Split by-pass input (second input)
• Output DC leakage protection
• Separate DSP for inverter control
• Separate DSP for PFC
• 3-level battery protection
• High charging current capacity
• Charge / Discharge current indicator
• Advanced remote control features
• 5 years spare parts support
• 2-Year Warranty
Technicial Specifications
Nominal Power | 30 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 400x815x1040 |
Nominal Power | 40 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 515x855x1440 |
Nominal Power | 60 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 515x855x1440 |
Nominal Power | 80 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 515x855x1440 |
Nominal Power | 100 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 515x855x1440 |
Nominal Power | 160 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 825x855x1770 |
Nominal Power | 200 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 825x855x1770 |
Nominal Power | 250 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 825x855x1770 |
Nominal Power | 300 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 1250x1055x1900 |
Nominal Power | 400 kVA |
GENERAL | |
Power Factor | ≥ 0.99 |
Indicator | Phase-N Voltage, Phase-Phase Voltage, Current, Power, Crest Factor, Frequency, PF, Service time |
PRODUCTIVITY | |
Productivity | Up to 93% (at 100% load) |
INPUT | |
Voltage | 3~ 380 VAC |
Voltage Range | 380/400 VAC 3F + N + Earth, ± %20 (optional 415 VAC (+%15, -%25)) 3F + N + Earth ± %15 |
Frequency | 50Hz. / 60Hz. ± %5 |
Frequency Range | 40 - 70 Hz |
Protections | Fuses, Voltage and Frequency tolerance, Input power limitation, Phase reversal protection, Input breaker contactor |
Power Factor | ≥ 0.99 @ 100% load |
THDi | ≤ 3% |
OUTPUT | |
Voltage | 380/400 VAC 3F + N , ± %1 (optional 415 VAC ) |
Frequency | Synchronized to the network: ± 2% / Free operation: ± 0.1% |
Other Protections | Intelligent short circuit protection, voltage tolerance protection, DC balance, regenerative load, current limiting protections |
THDv | < %3 ( 100% linear load) |
Peak Factor | 3:1 |
Overload capacity | %100 - %125 load : 10 dk. - %125 - %150 load :1 dk. - > %150 load : by-pass |
BATTERY; | |
Voltage / (DC) / Quantity | ± 336 VDC (2X28 Battery) |
Battery Protection | 3 level alarm, Battery fuses, Charge current limitation, Heat compensated battery charging system (optional) |
COMMUNICATION | |
Port | Auto diagnostic, 3 maintenance indicators, calibration system from RS232, Hourmeter display 2xRS232 serial port, 4 standard and 8 optional dry contacts |
User Interface | 4 line LCD panel, Mimic led panel, 5 vector buttons, Buzer, Optional color TFT display. |
ENVIRONMENTAL CONDITIONS | |
Operating temperature | 0oC ~ 40oC |
Recommended Operating Temperature | 15oC ~ 25oC |
Storage Temperature | -25oC ~ 70oC |
Altitude / Relative Humidity | ≤1000, 1% reduction in every 100m / 0-95%, without condensation |
Noise Level | < 62 dBA |
STANDARD | |
Security / EMC / LVD / Performance | EN62040-1 , EN62040-2, EN62040-3 |
DIMENSIONS | |
Dimensions (GxDxY) [mm] | 1250x1055x1900 |